Through in‑depth research and engineering experience in various industries' cleanrooms, Berbson understands the critical points of cleanroom environmental control. We comprehensively build advanced dust‑free cleanroom spaces from the aspects of standards, professionalism, system integration, energy saving, intelligence, and convenience. We provide complete cleanroom turnkey services including cleanroom planning and design, personnel and material flow purification solutions, cleanroom building decoration systems, air purification systems, HVAC systems, pure water systems, specialty gas systems, electrical systems, plumbing systems, automatic control systems, compressed air systems, wastewater and exhaust gas systems, etc.

Gas purification equipment Pure water facility Finished product warehouse Specialty gas facility Cooling water equipment HVAC purification Cleanroom Material purification room Material storage Material entry Electrical facility Personnel purification Personnel entry Office & management
Air Cleanliness Reference Classes (Cosmetic Industry)
Class ≥0.5 μm (particles/m³) ≥5 μm (particles/m³) Sedimentation bacteria (CFU/plate) Airborne bacteria (CFU/m³)
1003,500015
10,000350,0002,0003100
100,0003,500,00020,00010500
300,00010,500,000≤60,00015

* Cosmetic cleanrooms often follow similar cleanliness standards to ensure product safety and hygiene.

Cosmetic Cleanroom Key Requirements

Microbial contamination control in cosmetic cleanrooms starts with production process and plant layout. Air quality in purification engineering, personnel management, and the required equipment and instruments are extremely important. In cleanroom production environments, cosmetic filling workshops must be designed according to GMP requirements.

Cosmetic Cleanroom Parameter Specifications
Air changes (Class 100,000) 10–15 times/hour
Air changes (Class 10,000) 15–25 times/hour
Air changes (Class 1,000) 50–52 times/hour
Class 100 workbench airflow 0.25–0.35 m/s
Pressure differential Main room to adjacent ≥5 Pa
Temperature (winter) >16°C ±2°C
Temperature (summer) <26°C ±2°C
Relative humidity 45–65% RH
Noise ≤65 dB(A)
Fresh air makeup 20–30% of total supply air
Illuminance ≥300 Lux